Investigation of the Effect of Harmonics Caused by Transformer-Induced Nonlinear Loads on Electrical Energy
Publication date
2025-05-30
Editors
Advisors
Supervisors
Document Type
Article
Metadata
Show full item recordCollections
License
cc_by_nc_sa
Abstract
In this study, distribution transformers in the Muş Alparslan University campus are analyzed in order to minimize energy losses due to harmonics in the electrical network. Current and voltage harmonics, which are the power quality problems of these transformers, are analyzed. The power quality of different transformers in Muş Alparslan University was measured with a Chauvin Arnoux CA:8331 energy analyzer. Three-phase nonlinear load models were created using current harmonic values in the Matlab/Simulink environment. A parallel active power filter is designed in the Matlab/Simulink environment to eliminate current harmonics. The performance of the parallel active power filter is analyzed for each transformer. As a result, the total harmonic distortion(THDI) ratio for the current decreased from 6.78% to 1.38% in fast Fourier transform analyses after the parallel active power filter was activated in the first transformer. Similarly, the THDI ratio decreased from 5.1% to 2.19% in the second transformer, from 4.5% to 1.39% in the third transformer, and from 5.63% to 1.36% in the fourth transformer.
Keywords
active parallel power filter, energy quality, Harmonics, Matlab/Simulink, General Engineering, Applied Mathematics
Citation
Rüstemli, S, Sezgin, N, Coşkun, B & Şahin, G 2025, 'Investigation of the Effect of Harmonics Caused by Transformer-Induced Nonlinear Loads on Electrical Energy', Revista Internacional de Metodos Numericos para Calculo y Diseno en Ingenieria, vol. 41, no. 2, 30. https://doi.org/10.23967/J.RIMNI.2025.10.64634