Classroom ventilation and indoor air quality - Results from the FRESH intervention study

Publication date

2016-08

Authors

Rosbach, JeannetteISNI 0000000395930632
Krop, E.J.M.ISNI 0000000390046063
Vonk, Machiel
van Ginkel, J.W.ISNI 0000000393105161
Meliefste, KeesISNI 0000000492910940
Wind, Siegfried
Gehring, UlrikeORCID 0000-0003-3612-5780ISNI 0000000097926870
Brunekreef, BertISNI 0000000029543122

Editors

Advisors

Supervisors

Document Type

Article
Open Access logo

License

taverne

Abstract

Inadequate ventilation of classrooms may lead to increased concentrations of pollutants generated indoors in schools. The FRESH study, on the effects of increased classroom ventilation on indoor air quality, was performed in 18 naturally ventilated classrooms of 17 primary schools in the Netherlands during the heating seasons of 2010-2012. In 12 classrooms, ventilation was increased to targeted CO2 concentrations of 800 or 1200 ppm, using a temporary CO2 controlled mechanical ventilation system. Six classrooms were included as controls. In each classroom, data on endotoxin, ß(1,3)-glucans, particles with diameters of less than 10 μm (PM10 ), and less than 2.5 μm (PM2.5 ) and nitrogen dioxide (NO2 ) were collected during three consecutive weeks. Associations between the intervention and these measured indoor air pollution levels were assessed using mixed models, with random classroom-effects. The intervention lowered endotoxin and ß(1,3)-glucan levels and PM10 concentrations significantly. PM10 for instance, was reduced by 25 μg/m³ (95% confidence interval 13-38 μg/m³) from 54 μg/m³ at maximum ventilation rate. No significant differences were found between the two ventilation settings. Concentrations of PM2.5 and NO2 were not affected by the intervention. Our results provide evidence that increasing classroom ventilation is effective in decreasing the concentrations of some indoor generated pollutants. This article is protected by copyright. All rights reserved.

Keywords

Taverne

Citation

Rosbach, J, Krop, E, Vonk, M, van Ginkel, J, Meliefste, K, Wind, S, Gehring, U & Brunekreef, B 2016, 'Classroom ventilation and indoor air quality - Results from the FRESH intervention study', Indoor Air, vol. 26, no. 4, pp. 538-545. https://doi.org/10.1111/ina.12231